Key Commercial Data
Orderkey | 2905415 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 33 (C-4-2017) |
GTIN | 4055626045887 |
Weight per Piece (excluding packing) | 724.000 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Ambient conditions
Degree of protection | IP20 (only when all terminal points are used) |
---|---|
Ambient temperature (operation) | -40 °C … 80 °C |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % … 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (5 – 500 Hz/2.5 h/X, Y, Z) |
General
IEC test classification | I / II |
---|---|
T1 / T2 | |
T1 | |
I | |
EN type | T1 / T2 |
T1 | |
IEC power supply system | TN-S |
TT | |
Mode of protection | L-N |
L-PE | |
N-PE | |
Mounting type | DIN rail: 35 mm |
Color | light grey RAL 7035 |
traffic grey A RAL 7042 | |
Housing material | PA 6.6-FR 20% GF |
PBT-FR | |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Number of positions | 2 |
Surge protection fault message | Optical, remote indicator contact |
Protective circuit
Nominal voltage UN | 240 V AC (TN-S) |
---|---|
240 V AC (TT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 350 V AC |
Rated load current IL | 125 A (< 55 °C) |
Residual current IPE | ≤ 0.01 mA |
Nominal discharge current In(8/20) µs (L-N) | 25 kA |
Nominal discharge current In(8/20) µs (L-PE) | 25 kA |
Nominal discharge current In(8/20) µs (N-PE) | 100 kA |
Maximum discharge current Imax(8/20) µs (L-N) | 50 kA |
Maximum discharge current Imax(8/20) µs (L-PE) | 50 kA |
Impulse discharge current (10/350) µs (L-N), charge | 12.5 As |
Impulse discharge current (10/350) µs (L-N), specific energy | 160 kJ/Ω |
Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 25 kA |
Impulse discharge current (10/350) µs (L-PE), charge | 12.5 As |
Impulse discharge current (10/350) µs (L-PE), specific energy | 160 kJ/Ω |
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 25 kA |
Impulse discharge current (10/350) µs (N-PE), charge | 50 As |
Impulse discharge current (10/350) µs (N-PE), specific energy | 2500 kJ/Ω |
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 100 kA |
Total discharge current Itotal(10/350) µs | 50 kA |
Follow current interrupt rating Ifi(L-N) | 50 kA |
Follow current interrupt rating Ifi(N-PE) | 100 A |
Short-circuit current rating ISCCR | 50 kA |
Voltage protection level Up(L-N) | ≤ 1.5 kV |
Voltage protection level Up(L-PE) | ≤ 2.5 kV |
Voltage protection level Up(N-PE) | ≤ 1.5 kV |
Residual voltage Ures(L-N) | ≤ 1.5 kV (at In) |
Residual voltage Ures(L-PE) | ≤ 2.5 kV (at In) |
Residual voltage Ures(N-PE) | ≤ 1.5 kV (at In) |
TOV behavior at UT(L-N) | 415 V AC (5 s / withstand mode) |
457 V AC (120 min / withstand mode) | |
TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
Response time tA | ≤ 100 ns |
Max. backup fuse with V-type through wiring | 125 A (gG) |
Max. backup fuse with branch wiring | 315 A (gG) |
Additional technical data
Follow current quenching capacity Ifi(L-N) | 100 kA (264 V AC) |
---|---|
Short-circuit current rating ISCCR | 100 kA (264 V AC) |
Maximum discharge current Imax(8/20) µs | 100 kA (AS NZS 1768:2007) |