Key Commercial Data
Orderkey | 2859913 |
---|---|
Packing unit | 10 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 28 (C-6-2013) |
GTIN | 4046356045520 |
Weight per Piece (excluding packing) | 249.650 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -40 °C … 80 °C |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % … 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (5 – 500 Hz/2.5 h/X, Y, Z) |
General
IEC test classification | I / II |
---|---|
T1 / T2 | |
EN type | T1 / T2 |
IEC power supply system | TT |
Mode of protection | L-N |
L-PEN | |
Mounting type | on base element |
Color | gray/blue |
Housing material | PBT |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | Male |
Number of positions | 1 |
Surge protection fault message | optical |
Protective circuit
Nominal voltage UN | 240 V AC (TN) |
---|---|
240 V AC (TT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous voltage UC | 350 V AC |
Nominal discharge current In(8/20) µs | 25 kA |
Maximum discharge current Imax(8/20) µs | 50 kA |
Impulse discharge current (10/350) µs, charge | 12.5 As |
Impulse discharge current (10/350) µs, specific energy | 160 kJ/Ω |
Impulse discharge current (10/350) µs, peak value limp | 25 kA |
Follow current interrupt rating Ifi | 50 kA |
Short-circuit current rating ISCCR | 50 kA |
Voltage protection level Up | ≤ 1.5 kV |
Residual voltage Ures | ≤ 1.5 kV (at In) |
Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
TOV behavior at UT | 415 V AC (5 s / withstand mode) |
457 V AC (120 min / withstand mode) | |
Response time tA | ≤ 100 ns |
Max. backup fuse with branch wiring | 315 A (gG) |
UL specifications
SPD Type | 4CA |
---|---|
Maximum continuous operating voltage MCOV (L-N) | 264 V AC |
Nom. voltage | 240 V AC |
Mode of protection | L-N |
Power distribution system | Split phase |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-N) | 1350 V |
Nominal discharge current In(L-N) | 20 kA |