Key Commercial Data
| Orderkey | 1026043 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626519111 |
| Weight per Piece (excluding packing) | 200.000 g |
| Custom tariff number | 85369095 |
| Country of origin | US (United States) |
Dimensions
| Dimensional drawing |
![]() |
|---|---|
| Caption | Image shows FB-12SP |
| Width | 254.1 mm |
| Height | 112.5 mm |
| Depth | 83.5 mm |
Ambient conditions
| Ambient temperature (operation) | -50 °C … 90 °C |
|---|---|
| Ambient temperature (storage/transport) | -50 °C … 90 °C |
| Permissible humidity (operation) | 5 % … 95 % (non-condensing) |
| Permissible humidity (storage/transport) | non-condensing |
| Altitude | 2000 m |
| Degree of protection | IP20 |
General
| Mounting position | On horizontal and vertical DIN rail NS 35 in acc. with EN 60715 |
|---|---|
| Net weight | 0 g |
| MTTF | 723 Years (25 degrees C) |
| Conformance | CE-compliant, additionally EN 61326 |
| UL, USA | ANSI/UL 61010-1 |
| Fieldbus Foundation | FF-846 |
Power supply
| Supply voltage range | 10.6 V DC … 32 V DC (input on trunk line side) |
|---|---|
| Typical current consumption | 6.5 mA |
| Conductor cross section flexible max. | 0.20 mm² |
| Conductor cross section flexible min. | 2.50 mm² |
| Conductor cross section solid max. | 0.20 mm² |
| Conductor cross section solid min. | 2.50 mm² |
| Max. AWG conductor cross section, flexible | 12 |
| Min. AWG conductor cross section, flexible | 24 |
| Conductor cross section AWG max. | 12 |
| Conductor cross section AWG min. | 24 |
Serial interface
| Interface 1 | Foundation Fieldbus and PROFIBUS PA Segment |
|---|---|
| No. of ports | 8 |
| Connection method | Pluggable COMBICON screw connection for each spur |
| Termination resistor | 100 Ω (external removable plug) |
| 100 Ω, external removable plug included | |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Output nominal voltage | ≤ 32 V (each spur) |
| Output current | 38 mA |
| Inductance Li | 4 µH |
| Max. output voltage Uo | Uin(spur) |
Safety data
| Input voltage Ui | 32 V (IIB (C/D)) |
|---|---|
| Max. output voltage Uo | Uin(spur) |
| Max. output current Io | 56 mA (spur) |
| Max. output power Po | 1.792 W |
| Group | IIC/IIB |
| Max. external capacitance Co | 80 nF |
| Additional text | spur |
| Group | IIC/IIB |
| Max. external inductivity Lo | 0.26 mH |
| Additional text | spur |
| ATEX | Sira 13ATEX4247X; II 3(3)G Ex nA [ic] IIC T4 Gc, Entity/FISCO ic spurs Ex nA [nL] IIC T4 Gc; II 3G Ex ic IIC T4 Gc, FISCO ic |
| IECEx | IECEx SIR 13.0089X; Ex nA [ic] IIC T4 Gc, Entity/FISCO ic spurs; Ex nA [nL] IIC T4 Gc; Ex ic IIC T4 Gc, FISCO ic |
| UL, USA | Class I, Zone 2; AEx nA[ic] IIC T4, Entity/FISCO spurs Class I, Div. 2, Groups A, B, C, D; T4 |
| CSA, USA/Canada | Class I, Div. 2, Groups A, B, C, D; Ex nA [nL] IIC T4; Class I, Zone 2, AEx nA [nC] IIC T4 |
Standards and Regulations
| Type of test | Corrosive resistance in acc. to ANSI-ISA 71.04-1985 – Severity level G3 |
|---|---|
| Designation | Standards/regulations |
| Standards/regulations | Ring wave noise immunidty in acc. with IEC 61000-4-12 |
| Designation | Standards/regulations |
| Standards/regulations | Dry heat in acc. with IEC 61131-2 |
| Designation | Standards/regulations |
| Standards/regulations | Damp heat in acc. with IEC 61131-2 |
| Designation | Standards/regulations |
| Standards/regulations | Shock and vibration in acc. with EN 61131-2 and EN 50178 |
| IEC 61158-2 | |
| EN 60079-0:2011; EN 60079-11:2012; EN 60079-15:2005; EN 60079-15:2010 | |
| IEC 60079-0:2011; IEC 60079-11:2011; IEC 60079-15:2005; IEC 60079-15:2010 | |
| Flammability rating according to UL 94 | V0 |
| Shock | 30g, 11 ms |
| Vibration (operation) | 5g, 10 Hz … 150 Hz |
| Conformance | CE-compliant, additionally EN 61326 |
| UL, USA | ANSI/UL 61010-1 |
| Fieldbus Foundation | FF-846 |
| Group | IIC/IIB |
| IIC/IIB | |
| ATEX | Sira 13ATEX4247X; II 3(3)G Ex nA [ic] IIC T4 Gc, Entity/FISCO ic spurs Ex nA [nL] IIC T4 Gc; II 3G Ex ic IIC T4 Gc, FISCO ic |
| IECEx | IECEx SIR 13.0089X; Ex nA [ic] IIC T4 Gc, Entity/FISCO ic spurs; Ex nA [nL] IIC T4 Gc; Ex ic IIC T4 Gc, FISCO ic |
| UL, USA | Class I, Zone 2; AEx nA[ic] IIC T4, Entity/FISCO spurs Class I, Div. 2, Groups A, B, C, D; T4 |
| CSA, USA/Canada | Class I, Div. 2, Groups A, B, C, D; Ex nA [nL] IIC T4; Class I, Zone 2, AEx nA [nC] IIC T4 |
Classifications
[email protected]
| [email protected] 4.0 | 27250203 |
|---|---|
| [email protected] 4.1 | 27250203 |
| [email protected] 5.0 | 27250203 |
| [email protected] 5.1 | 27259200 |
| [email protected] 6.0 | 27242600 |
| [email protected] 7.0 | 27242610 |
| [email protected] 8.0 | 27242610 |
| [email protected] 9.0 | 27242610 |
ETIM
| ETIM 2.0 | EC001423 |
|---|---|
| ETIM 3.0 | EC001600 |
| ETIM 4.0 | EC001600 |
| ETIM 5.0 | EC001600 |
| ETIM 6.0 | EC001600 |
| ETIM 7.0 | EC001600 |