Key Commercial Data
| Orderkey | 2903914 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 30 (C-5-2017) |
| GTIN | 4046356771375 |
| Weight per Piece (excluding packing) | 217.700 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
Note
| Type of note | Notes on operation |
|---|---|
| Note | If this device is to be used in combination with the CrossPowerSystem power distribution board, the device mount for the 16 A fuse (order designation: EM-CPS-DA-22,5F/16A; order number: 1002668) is required in order to attach the hybrid motor starter to the power distribution board. |
Ambient conditions
| Ambient temperature (operation) | -25 °C … 70 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C … 80 °C |
| Degree of protection | IP20 |
Device supply
| Rated control circuit supply voltage US | 24 V DC |
|---|---|
| Control supply voltage range | 19.2 V DC … 30 V DC |
| Rated control supply current IS | 40 mA |
| Type of protection | Surge protection |
| Reverse polarity protection |
Input data
| Input name | Control input |
|---|---|
| Rated actuating voltage UC | 24 V DC |
| Triggering voltage range | 19.2 V DC … 30 V DC |
| Rated actuating current IC | 5 mA (Input type 1) |
| Switching threshold | 9.6 V (“0” signal) |
| 19.2 V (“1” signal) | |
| Switching level | < 5 V DC (For EMERGENCY STOP) |
| Typical turn-off time | < 30 ms |
| Type of protection | Reverse polarity protection |