Key Commercial Data
| Orderkey | 2902352 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 208 (C-5-2017) |
| GTIN | 4046356657136 |
| Weight per Piece (excluding packing) | 813.100 g |
| Custom tariff number | 90303100 |
| Country of origin | TN (Tunisia) |
Dimensions
| Width | 96 mm |
|---|---|
| Height | 96 mm |
| Depth | 82 mm |
| Installation depth with extension module | 80 mm |
| Installation depth without extension module | 60 mm |
Ambient conditions
| Ambient temperature (operation) | -10 °C … 55 °C (14 °F to 131 °F) |
|---|---|
| Ambient temperature (storage/transport) | -20 °C … 85 °C (-4 °F … 185 °F) |
| Max. permissible relative humidity (operation) | ≤ 95 % |
| Max. salt spray content | ≤ 2.5 % |
Input data
| Measuring principle | True r.m.s. value measurement |
|---|---|
| Acquisition of harmonics | up to 63rd harmonic |
| Measured value | AC sine (50/60 Hz) |
| Input name | Voltage measuring input V1, V2, V3 |
| Input voltage range | 18 V AC … 700 V AC (Phase/Phase) |
| 11 V AC … 404 V AC (Phase/neutral conductor) | |
| Input voltage | 500 kV AC (Primary, via external voltage transducers) |
| Secondary: 60, 100, 110, 115, 120, 173, 190 V AC | |
| Precision | 0.2 % |
| Input current range | via external transformers |
| Input current | 9999 A (primary) |
| 1 A and 5 A, secondary | |
| Current measuring range | 0 A … 9999 A |
| Overload capacity | 6 A (Permanent) |
| Response threshold from measuring range nominal value | 10 mA |
| Precision | 0.2 % |
| Current overload | 10 x INfor 1 s |
| Messbereich_Leistung | 0 MW … 8000 MW |
| 0 Mvar … 8000 Mvar | |
| 0 MVA … 8000 MVA | |
| Precision | 0.5 % |
| Active energy (IEC 62053-22) | Class 0.5 S |
| Reactive power (IEC 62053-23) | Class 2 |
| Voltage input signal | Via extension module |