Key Commercial Data
| Orderkey | 2905849 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626000855 |
| Weight per Piece (excluding packing) | 398.400 g |
| Custom tariff number | 90303330 |
| Country of origin | IT (Italy) |
Ambient conditions
| Ambient temperature (operation) | -25 °C … 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -30 °C … 70 °C |
| Max. permissible relative humidity (operation) | < 90 % |
| Permissible humidity (storage/transport) | 0 % … 90 % |
Input data
| Measuring principle | True r.m.s. value measurement |
|---|---|
| Measured value | AC sine (50/60 Hz) |
| Input name | Measuring input |
| Input voltage range | 196 V AC … 460 V AC (Phase/Phase) |
| 113 V AC … 265 V AC (Phase/neutral conductor) | |
| Surge voltage capacity | 460 V AC (Permanent) |
| Precision | 0.5 % (Phase/neutral conductor) |
| Input name | Current measuring input I1, I2, I3 |
| Input current | 10 A (scaled nominal current) |
| 65 A (Imax) | |
| Overload capacity | 1920 A (10 ms) |
| Precision | 0.5 % |
| 1 % (Effective and apparent power) | |
| Reactive power (IEC 62053-23) | Class 2 |
| Description of the input | Digital input |
| Number | 3 |
| Voltage input signal | 5 V DC ±5 % |
General
| Display | LCD display |
|---|---|
| Measuring rate | 750 ms |
| Supply voltage range | Measurement voltage supply |
| Power consumption | ≤ 12 VA (2 W) |
| Mains type | 3-phase (4-conductor) |
| Color | black |
| Conformance | CE-compliant |
| Rated insulation voltage | 300 V AC (EN 61010-1) |
| Overvoltage category | III |
| Test voltage | 4 kV AC (50 Hz, 1 min.) |