Key Commercial Data
Orderkey | 2796121 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 126 (TT-2007) |
GTIN | 4017918073312 |
Weight per Piece (excluding packing) | 1.190 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
General
Housing material | Aluminum |
---|---|
Color | black |
Standards for cearances and creepage distances | VDE 0110-1 |
IEC 60664-1 | |
Mounting type | Connection-specific intermediate plugging |
Type | Attachment plug |
Direction of action | Line-Line & Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
Protective circuit
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
VDE requirement class | C1 |
C2 | |
C3 | |
D1 | |
Maximum continuous voltage UC | 12 V DC |
Nominal current IN | 175 mA (25 °C) |
Operating effective current ICat UC | ≤ 10 µA |
Residual current IPE | ≤ 4 µA |
Nominal discharge current In(8/20) µs (line-line) | 5 kA |
Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
Nominal discharge current In(8/20) µs (core-signal ground) | 5 kA |
Total surge current (8/20) µs | 10 kA |
Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 22 V |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 600 V |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 22 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 600 V |
Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 22 V |
Residual voltage at In(line-line) | ≤ 17 V |
Residual voltage at In(line-signalground) | ≤ 33 V |
Voltage protection level Up(line-line) | ≤ 25 V (C2 – 4 kV / 2 kA) |
≤ 30 V (C2 – 10 kV / 5 kA) | |
Voltage protection level Up(line-earth) | ≤ 700 V (C2 – 10 kV / 5 kA) |
Voltage protection level Up(line-signalground) | ≤ 30 V (C2 – 4 kV / 2 kA) |
Response time tA(line-line) | ≤ 1 ns |
Response time tA (line-signalground) | ≤ 1 ns |
Response time tA(line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | 3.2 dB (≤ 1 MHz) |
0.4 dB (≤ 600 kHz) | |
Input attenuation aE, asym. | 1.7 dB (≤ 1 MHz) |
0.1 dB (≤ 600 kHz) | |
Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 5 MHz |
Cut-off frequency fg (3 dB), sym. in 600 Ohm system | typ. 500 kHz |
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system | typ. 5 MHz |
Cut-off frequency fg (3 dB), asym. (PE) in 600 Ohm system | typ. 500 kHz |
Resistance in series | 22 Ω |
Surge protection fault message | none |
Impulse durability (line-line) | C2 – 10 kV/5 kA |
Impulse durability (line-earth) | C2 – 10 kV/5 kA |
D1 – 2.5 kA |
Connection data
Connection method | D-SUB-15 |
---|---|
Connection method IN | D-SUB-15 socket |
Connection method OUT | D-SUB-15 connector |
Connection technology | V.11 |