General
Housing material | Aluminum |
---|---|
Color | black |
Standards for cearances and creepage distances | VDE 0110-1 |
IEC 60664-1 | |
Mounting type | Connection-specific intermediate plugging |
Type | Attachment plug |
Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
IEC test classification | C2 |
---|---|
C3 | |
D1 | |
VDE requirement class | C2 |
C3 | |
D1 | |
Maximum continuous voltage UC | 7 V DC |
Nominal current IN | 1.5 A (25 °C) |
Operating effective current IC at UC | ≤ 1 mA |
Residual current IPE | ≤ 4 µA |
Nominal discharge current In (8/20) µs (line-line) | 350 A |
Nominal discharge current In (8/20) µs (line-earth) | 2.5 kA |
Total surge current (8/20) µs | 10 kA |
Max. discharge current Imax (8/20) µs maximum (line-earth) | |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
Output voltage limitation at 1 kV/µs (line-line) static | ≤ 20 V |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 450 V |
Residual voltage at In (line-line) | ≤ 50 V |
Residual voltage at In (line-earth) | ≤ 25 V |
Voltage protection level Up (line-line) | ≤ 50 V |
Voltage protection level Up (line-earth) | ≤ 600 V |
Response time tA (line-line) | ≤ 500 ns |
Response time tA (line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | 0.1 dB (≤ 10 MHz) |
Cut-off frequency fg (3 dB), sym. in 100 Ohm system | ≥ 100 MHz |
Capacity (line-line) | 20 pF (f=1 MHz / VR= 0 V) |
Resistance in series | |
Surge protection fault message | none |
Impulse durability (line-line) | C1 – 500 V / 250 A |
Impulse durability (line-earth) | C2 – 10 kV/5 kA |
D1 – 1 kA |
Connection data
Connection method | RJ45 |
---|---|
Connection method IN | RJ45 socket |
Connection method OUT | RJ45 socket |