Key Commercial Data
Orderkey | 2905744 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 314 (C-4-2017) |
GTIN | 4046356992367 |
Weight per Piece (excluding packing) | 325.000 g |
Custom tariff number | 85362010 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -25 °C … 70 °C (Startup at -40 C type-tested) |
---|---|
-25 °C … 65 °C (for UL 2367) | |
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Humidity test | 240 h, 95 % RH, 40 °C |
Altitude | ≤ 6000 m (amsl (above mean sea level)) |
Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
Vibration (operation) | 5 Hz … 24.9 Hz (Amplitude ±1.6 mm; in accordance with IEC 60068-2-6, Test Fc) |
24.9 Hz … 150 Hz (Acceleration 4g; in accordance with IEC 60068-2-6, Test Fc with additional resonance frequency testing in accordance with DNV GL) | |
Degree of protection | IP20 |
General
Flammability rating according to UL 94 | V-0 |
---|---|
Mounting type | DIN rail: 35 mm |
Color | light grey RAL 7035 |
Number of positions | 8 |
Protection class | III |
Type | DIN rail module, one-piece |
Electrical data
Fuse type | electronic |
---|---|
Rated surge voltage | 0.5 kV |
Operating voltage | 18 V DC … 30 V DC |
Rated voltage | 24 V DC |
Rated current IN | max. 80 A DC (for double supply IN+ with at least 2 x 6 mm²) |
max. 70 A DC (for UL 2367) | |
0.5 / 1 / 2 / 4 / 6 / 10 A DC (adjustable per output channel) | |
Measuring tolerance I | typ. 40 % (0.5 A … 1 A) |
typ. 10 % (2 – 10 A) | |
Feedback resistance | max. 35 V DC |
Fail-safe element | 15 A DC (per output channel) |
Active current limitation | typ. 2.0 x IN(0.5 – 1 A) |
typ. 1.5 x IN(2 – 10 A) | |
Efficiency | > 99 % |
Closed circuit current I0 | typ. 50 mA |
Power dissipation | 1.2 W (No-load operation) |
17.2 W (Nominal operation) | |
Module initialization time | 3.3 s |
Waiting time after switch off of a channel | 10 s (at overload / short circuit) |
Temperature derating | 40 A DC (at 70°C (65°C for UL 2367)) |
50 A DC (at 60 °C) | |
60 A DC (at 50 °C) | |
70 A DC (at 40 °C) | |
80 A DC (at 40 °C) | |
70 A DC (at 40°C for UL 2367) | |
Tripping method | E (electronic) |
Required backup fuse | not required, integrated failsafe element |
Dielectric strength | max. 30 V DC (Load circuit) |
MTBF (IEC 61709, SN 29500) | 1304293 h (at 25 °C) |
858501 h (at 40 °C) | |
440048 h (at 60°C) | |
Shutdown time load circuit | 0.02 s (> 1.3 x IN) |
30 s (1.1 … 1.3 x IN) | |
Undervoltage shutdown load circuit | ≤ 17.8 V DC (active) |
≥ 19 V DC (inactive) | |
Surge voltage shutdown load circuit | ≥ 30.5 V DC (active) |
≤ 29.5 V DC (inactive) | |
Max. capacitive load load circuit | 75000 µF (per channel at 24 V DC) |
Output voltage status output | 24 V DC |
Output current status output | max. 20 mA (when I > 80% at at least one channel) |
Input voltage reset input | 7 V DC … 30 V DC (Reset with falling edge) |
Current consumption reset input | typ. 0.4 mA (at 24 V DC) |
Remote indication contact
Connection name | Remote indication circuit |
---|---|
Switching function | N/O contact |
Stripping length | 10 mm |
Conductor cross section solid | 0.2 mm² … 2.5 mm² |
Conductor cross section AWG | 24 … 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 1.5 mm² … 0.25 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² … 2.5 mm² |
DC operating voltage | 0 V DC … 30 V DC |
DC operating current | 1 mA DC … 100 mA DC |