Key Commercial Data
Orderkey | 2800869 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 328 (C-4-2017) |
GTIN | 4046356690348 |
Weight per Piece (excluding packing) | 71.600 g |
Custom tariff number | 85362010 |
Country of origin | ID (Indonesia) |
Ambient conditions
Ambient temperature (operation) | -30 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Humidity test | 240 h, 95 % RH, 40 °C |
Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
Vibration (operation) | 8g (IEC 60068-2-6, Test Fc) |
Degree of protection | IP30 (Actuation area) |
General
Installation instructions | When mounted in rows, the nominal device current can be limited to just 80% or must be overdimensioned accordingly. |
---|---|
Flammability rating according to UL 94 | V0 |
Mounting type | on base element |
Color | gray |
Number of positions | 2 |
Insulating material group | II |
Degree of pollution | 2 |
Type | Male |
Electrical data
Fuse type | SFB |
---|---|
Rated surge voltage | 2.5 kV (Increased insulation in actuation area) |
Rated voltage | 80 V DC (IEC 60934) |
80 V DC (UL 1077) | |
80 V DC (UL 508 – with plug-in base) | |
Rated current IN | 1 A (IEC 60934) |
inductive load according to UL 1077 | |
1 A DC (low-induction load according to UL 1077) | |
1 A DC (inductive load according to UL 508 – with plug-in base) | |
1 A DC (low-induction load according to UL 508 – with plug-in base) | |
Rated insulation voltage Ui | 277 V AC (UL 1077) |
250 V AC (IEC 60934) | |
Power dissipation | 1.1 W (in nominal operation per channel) |
Device resistance | 1100 mΩ |
Insulation resistance Riso | > 100 MΩ (500 V DC) |
Type of actuation | S type |
Tripping method | TM (thermomagnetic) |
Tripping level | Trip-free mechanism (positive) |
Rated short-circuit switching capacity Icn | |
600 A (80 V DC) | |
Required backup fuse | 15 A (I > Icn) |
Short-circuit switching capacity Ik | 1000 A AC (277 V AC) |
1000 A DC (50 V DC) | |
Dielectric strength | 3000 V AC (Actuation area) |
1500 V AC (Main to auxiliary circuit) | |
1500 V AC (Open main circuit) | |
1000 V AC (Open auxiliary circuit) | |
1500 V AC (Position to position) | |
Voltage drop | 1.1 V (at 1 x In) |
Switching cycles, max. | 6000 (240 V AC/1 x In) |
3000 (80 V DC/1 x In) | |
Auxiliary circuit | 277 V AC / 0.5 A (Low-induction) |
277 V AC / 1 A (Low-induction, maximum of 2000 cycles) | |
50 V DC / 1 A (Low-induction) | |
Minimum auxiliary contact operating voltage | 10 V |
Maximum auxiliary contact operating voltage | 240 V |
240 V | |
Minimum auxiliary contact operating current | 10 mA |
Maximum auxiliary contact operating current | 1 A |
Standards and Regulations
Standards/specifications | EN 60934 |
---|---|
UL 1077 UL/C-UL recognized | |
UL 508 UL/C – UL listed | |
CSA 22.2 No. 235-04 |