Key Commercial Data
Orderkey | 2800922 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 323 (C-4-2017) |
GTIN | 4046356690782 |
Weight per Piece (excluding packing) | 35.000 g |
Custom tariff number | 85362010 |
Country of origin | DE (Germany) |
Dimensions
Height | 45 mm |
---|---|
Width | 12.3 mm |
Depth | 52 mm |
Complete module height | 90 mm |
Complete module width | 12.3 mm |
Complete module depth | 77.3 mm |
Ambient conditions
Ambient temperature (operation) | -25 °C … 50 °C (non-condensing) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 70 °C |
Humidity test | 96 h, 95 % RH, 40 °C |
Vibration (operation) | 3g (In accordance with IEC 60068-2-6, Test Fc) |
Degree of protection | IP30 (Actuation area) |
General
Installation instructions | When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor). Special precautionary measures must be taken in systems or machines, to prevent components from restarting (e.g., use of a safety PLC). Parallel connection of multiple circuit breakers is not permitted. |
---|---|
Flammability rating according to UL 94 | V0 |
Mounting type | on base element |
Color | gray |
Number of positions | 1 |
Degree of pollution | 2 |
Type | Male |
Electrical data
Fuse type | electronic |
---|---|
Rated surge voltage | 0.5 kV |
Operating voltage | 24 V DC |
18 V DC … 30 V DC | |
Nominal current IN | 1 A |
Active current limitation | typ. 1.25 x IN |
Closed circuit current I0 | typ. 8 mA (When switched on) |
typ. 11 mA (With status output) | |
Power dissipation | 0.4 W (Nominal operation) |
Temperature derating | 1 A (at 50 °C) |
Tripping method | E (electronic) |
Required backup fuse | not required, integrated failsafe element |
Dielectric strength | max. 30 V DC (Load circuit) |
Voltage drop | 140 mV (at IN) |
Shutdown time load circuit | 800 ms (see time/current characteristic curve) |
Undervoltage shutdown load circuit | < 14 V (typ. OFF) |
> 17 V (typ. ON) | |
Max. capacitive load load circuit | 20000 µF |
Output voltage status output | 24 V DC |
Output current status output | max. 0.2 A (Short-circuit-proof) |
Auxiliary type of contact | Positive-switching signal output |
Standards and Regulations
Standards/specifications | UL 2367 UL recognized |
---|---|
UL 508 UL/C-UL listed | |
EMV EN 61000-6-3 Interference emission | |
EMV EN 61000-6-2 Noise immunity |