Key Commercial Data
Orderkey | 3281113 |
---|---|
Packing unit | 50 pc |
Minimum order quantity | 50 pc |
Catalog page | Page 389 (C-1-2017) |
GTIN | 4055626268958 |
Weight per Piece (excluding packing) | 8.950 g |
Custom tariff number | 85369010 |
Country of origin | IN (India) |
General
Number of levels | 1 |
---|---|
Number of connections | 4 |
Potentials | 1 |
Nominal cross section | 2.5 mm² |
Color | gray |
Insulating material | PC |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 8 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | IIIa |
Maximum power dissipation for nominal condition | 0.77 W |
Ambient temperature (operation) | -40 °C … 110 °C |
Maximum load current | 24 A (The maximum load current must not be exceeded by the total current of all connected conductors.) |
Nominal current IN | 24 A |
Nominal voltage UN | 690 V |
Open side panel | Yes |
Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
Back of the hand protection | guaranteed |
Finger protection | guaranteed |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 9.8 kV |
Result of power-frequency withstand voltage test | Test passed |
Power frequency withstand voltage setpoint | 1.89 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of bending test | Test passed |
Bending test rotation speed | 10 rpm |
Bending test turns | 135 |
Bending test conductor cross section/weight | 0.14 mm² / 0.2 kg |
2.5 mm² / 0.7 kg | |
Tensile test result | Test passed |
Conductor cross section tensile test | 0.14 mm² |
Tractive force setpoint | 10 N |
Conductor cross section tensile test | 2.5 mm² |
Tractive force setpoint | 40 N |
Result of tight fit on support | Test passed |
Tight fit on carrier | NS 35 |
Setpoint | 1 N |
Result of voltage-drop test | Test passed |
Requirements, voltage drop | ≤ 3.2 mV |
Result of temperature-rise test | Test passed |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 2.5 mm² |
Short-time current | 0.3 kA |
Result of thermal test | Test passed |
Ageing test for screwless modular terminal block temperature cycles | 192 |
Proof of thermal characteristics (needle flame) effective duration | 30 s |
Result of aging test | Test passed |
Oscillation, broadband noise test result | Test passed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum | Service life test category 2, bogie-mounted |
Test frequency | f1= 5 Hz to f2= 250 Hz |
ASD level | 6.12 (m/s2)2/Hz |
Acceleration | 3.12 g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock test result | Test passed |
Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form | Half-sine |
Acceleration | 30g |
Shock duration | 18 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Connection data
Connection method | Push-in connection |
---|---|
Connection in acc. with standard | IEC 60947-7-1 |
Conductor cross section solid min. | 0.14 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 14 |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Min. AWG conductor cross section, flexible | 26 |
Max. AWG conductor cross section, flexible | 16 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 1.5 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 1.5 mm² |
Stripping length | 10 mm … 12 mm |
Connection data (JIS standard)
Connection method | Push-in connection |
---|---|
Connection in acc. with standard | JIS 8207-7-1 |
Single-wire/terminal point, solid diameter min. | 0.5 mm |
Single-wire/terminal point, solid diameter max. | 1.6 mm |
Conductor cross section flexible min. | 0.5 mm² |
Conductor cross section flexible max. | 2 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 2 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 2 mm² |
Connection cross sections directly pluggable | 0.8 mm 1.6 mm |
Single-wire/terminal point, solid diameter min. | 0.8 mm |
Single-wire/terminal point, solid diameter max. | 1.6 mm |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 2 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 1.25 mm² |
Nominal current IN | 21 A |
Maximum load current | 21 A |
Nominal voltage UN | 600 V |
Standards and Regulations
Connection in acc. with standard | IEC 60947-7-1 |
---|---|
Flammability rating according to UL 94 | V0 |