Key Commercial Data
Orderkey | 2924346 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 131 (C-5-2017) |
GTIN | 4046356515443 |
Weight per Piece (excluding packing) | 122.400 g |
Custom tariff number | 85437090 |
Country of origin | DE (Germany) |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|
Ambient conditions
Ambient temperature (operation) | -20 °C … 60 °C (Any mounting position) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Maximum altitude | ≤ 2000 m |
Permissible humidity (operation) | 5 % … 95 % (non-condensing) |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
Sensor types that can be used (TC) | E, J, K, N as per IEC / EN 60584, L as per DIN 43760 |
---|---|
Temperature measuring range | -250 °C … 1372 °C (Range depending on the sensor type) |
Input signal range | -20 mV … 70 mV |
Measuring range span | Min. 50 K for thermocouples, 3 mV for mV sources |
Output data
Signal output | Current output |
---|---|
Configurable/programmable | Yes |
Current output signal | 0 mA … 20 mA |
4 mA … 20 mA | |
Load/output load current output | max. 500 Ω |
Output ripple (current) | < 50 µAPP |
Behavior in the event of a sensor error | As per NE 43 or can be freely defined |
Configurable/programmable | no |