Key Commercial Data
| Orderkey | 2917515 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 277 (C-5-2017) |
| GTIN | 4046356367677 |
| Weight per Piece (excluding packing) | 50.900 g |
| Custom tariff number | 85364900 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C … 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C … 80 °C |
| Permissible humidity (operation) | 15 % … 85 % |
| Noise immunity | EN 61000-6-2 |
| When being exposed to interference, there may be minimal deviations. |
Coil side
| Input voltage range | 24 V DC (19.2 V DC …30 V DC) |
|---|---|
| Function | F: Flashing beginning with pulse |
| Time setting range | 0.3 min. … 30 min. |
Contact side
| Contact type | 1 floating PDT |
|---|---|
| Interrupting rating (ohmic load) max. | 1125 VA (4.5 A/250 V AC, module mounted in rows, spacing ≤ 5 mm) |
| Output fuse | 6.3 A (fast-blow) |
General
| Status display | Green LED (POWER) |
|---|---|
| Yellow LED (relay active) | |
| Mechanical service life | approx. 2x 107cycles |
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Color | gray |
| Housing insulation material | Polyamide PA, self-extinguishing |
| Permissible humidity (operation) | 15 % … 85 % |
| Rated insulation voltage | 300 V AC (acc. to EN 50178) |
| Conformance | CE-compliant |
| ATEX | II 3 G Ex nA nC IIC T4 Gc X |
| UL, USA/Canada | UL/C-UL listed UL 508 |
| GL | GL EMC 1 C |