Ambient conditions
| Ambient temperature (operation) | -20 °C … 65 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | typ. 5 % … 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
| Shock | 15g, according to IEC 60068-2-27 |
| Vibration (operation) | 5g, accordance to IEC 60068-2-6 |
Input data
| Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
|---|---|
| Sensor types that can be used (TC) | B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG |
| Temperature measuring range | -200 °C … 850 °C |
| Input signal range | 0 Ω … 50 kΩ |
| Potentiometer resistance range | 0 Ω … 50 kΩ |
| Input signal range | -1000 mV … 1000 mV |
Output data
| Configurable/programmable | Yes |
|---|---|
| Current output signal | 4 mA … 20 mA (in the case of SIL; further free configuration without SIL) |
| Max. current output signal | 22 mA |
| Load/output load current output | ≤ 600 Ω (20 mA) |
| Behavior in the event of a sensor error | according to NE 43 or freely configurable |
| Output name | Relay output |
| Output description | 1 SIL/PL |
| Configurable/programmable | Yes |
| Contact type | 2 PDT |
| Contact material | AgSnO2, hard gold-plated |
| Maximum switching voltage | 250 V AC (250 V DC) |
| Maximum inrush current | 2 A (250 V AC) |
| 2 A (28 V DC) | |
| 0.2 A (120 V DC) | |
| Mechanical service life | 1x 105 cycles |
Power supply
| Supply voltage range | 24 V … 230 V AC/DC (-20 %/+10 %, 50/60 Hz) |
|---|---|
| Typical current consumption | < 100 mA (24 V DC) |
| Power consumption | < 2.4 W |