Key Commercial Data
Orderkey | 2865599 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 166 (C-5-2017) |
GTIN | 4046356153898 |
Weight per Piece (excluding packing) | 211.400 g |
Custom tariff number | 85176200 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -20 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (non-condensing) |
Field devices interface (HART)
Channels | 16 or 32; adjustable using a switch |
---|---|
Connection method | Flat-ribbon cable, 14-pos. (inclusive) |
Signal | HART FSK |
HART specification | HART Field Communication Protocol Rev. 6.0 (downward compatible up to Rev 4.0); FSK Physical Layer Specification (Rev. 8.1) |
Data transmission display | Two yellow “Tx” and “Rx” “HART” LEDs |
Display error | Red “ERR” LED (flashes in case of an error in the HART bus) |
RS-485 interface
Connection method | D-SUB-9 female connector |
---|---|
Signal | RS-485 |
Data flow control/protocols | Compatible with OPC HART server, PDM, PRM, and FDT/DTM |
Number of HART multiplexers per bus segment | Max 31 |
Address setting | 0…127; using a rotary switch at the front |
Data rate | 9600 / 19200 / 38400 / 57600 [bps]; via rotary switch at the front |
Transmission length | ≤ 1200 m |
Display | Two yellow “Tx” and “Rx” “RS-485” LEDs |
General data
Supply voltage | 24 V DC |
---|---|
Supply voltage range | 18 V … 31.2 V |
Typical current consumption | 55 mA |
Nominal power consumption | 1.35 W |
Operating voltage display | Green “PWR” LED |
Undervoltage monitoring | Yes (no faulty devices / output states) |
Galvanic isolation of HART signal/RS-485 | 350 V AC |
Galvanic isolation of HART signals between each other | 100 V DC (capacitive) |
Galvanic isolation of HART signal/supply | 350 V AC |
Galvanic isolation of RS-485/supply | 350 V AC |
Error monitoring | Processor error: The “PWR” LED flashes; error in the HART communication: the “ERR” LED flashes |
Conformance | CE-compliant |