Key Commercial Data
Orderkey | 1078801 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 382 (C-5-2019) |
GTIN | 4055626796314 |
Weight per Piece (excluding packing) | 0.000 g |
Custom tariff number | 85364190 |
Country of origin | DE (Germany) |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|---|
Note | Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. |
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules | |
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip. | |
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. |
Ambient conditions
Ambient temperature (operation) | -40 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Maximum altitude | ≤ 2000 m |
Degree of protection | RT II (Relay) |
IP20 (Relay base) | |
≥ IP54 (Installation location) |
Coil side
Nominal input voltage UN | 12 V DC |
---|---|
Typical input current at UN | 33 mA |
Typical response time | 8 ms |
Typical release time | 10 ms |
Coil voltage | 12 V DC |
Protective circuit | Reverse polarity protection Polarity protection diode |
Free-wheeling diode Damping diode | |
Operating voltage display | Yellow LED |
Power dissipation for nominal condition | 0.4 W |
Contact side
Contact type | 1 N/O contact |
---|---|
Type of switch contact | Single contact |
Contact material | AgSnO2 |
Maximum switching voltage | 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC… or …FBST 500…) |
Minimum switching voltage | 12 V (at 100 mA) |
Min. switching current | 100 mA (at 12 V DC) |
Maximum inrush current | 80 A (for 20 ms) |
130 A (peak, at capacitive load, 230 V AC, 24 μF) | |
Limiting continuous current | 6 A |
10 A (the value is permissible if both connections 13, both connections 14 and both connections BB are bridged) | |
Interrupting rating (ohmic load) max. | 144 W (at 24 V DC) |
58 W (at 48 V DC) | |
48 W (at 60 V DC) | |
50 W (at 110 V DC) | |
80 W (at 220 V DC) | |
85 W (for 250 V DC) | |
1500 VA (for 250 V AC) | |
Interrupting rating (ohmic load) max. bridged | 240 W (for 24 V DC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.) |
2500 VA (for 250 V AC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.) | |
Switching capacity min. | 1200 mW |
Switching capacity | 2 A (at 24 V, DC13) |
0.2 A (at 110 V, DC13) | |
0.2 A (at 250 V, DC13) | |
6 A (at 24 V, AC15) | |
6 A (at 120 V, AC15) | |
6 A (at 250 V, AC15) |
General
Test voltage relay winding/relay contact | 4 kV AC (50 Hz, 1 min.) |
---|---|
Operating mode | 100% operating factor |
Mechanical service life | 3x 107cycles |
Mounting position | any |
Assembly instructions | In rows with zero spacing |
Connection data
Connection name | Coil side |
---|---|
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section solid | 0.14 mm² … 2.5 mm² |
Conductor cross section flexible | 0.14 mm² … 2.5 mm² |
0.2 mm² … 2.5 mm² (Single ferrule) | |
2x 0.5 mm² … 1 mm² (TWIN ferrule) | |
Conductor cross section AWG | 26 … 14 |
Connection data 2
Connection name | Contact side |
---|---|
Connection method | Push-in connection |
Stripping length | 8 mm |
Conductor cross section solid | 0.14 mm² … 2.5 mm² |
Conductor cross section flexible | 0.14 mm² … 2.5 mm² |
0.2 mm² … 2.5 mm² (Single ferrule) | |
2x 0.5 mm² … 1 mm² (TWIN ferrule) | |
Conductor cross section AWG | 26 … 14 |
Standards and Regulations
Designation | Standards/regulations |
---|---|
Standards/regulations | EN 50178 |
EN 61810-1 | |
Rated insulation voltage | 250 V AC |
Rated surge voltage | 6 kV |
Insulation | Safe isolation, reinforced insulation |
Pollution degree | 2 |
Overvoltage category | III |
Environmental Product Compliance
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |
Articles in set
Relay base PLC-BPT- 12DC/ 1IC/ACT 1090868
14 mm PLC basic terminal block for high switch-on currents with push-in connection, without relay or solid-state relay, for mounting on DIN rail NS 35/7,5, with load return line connection (BB), 1 N/O contact, input voltage: 12 V DC
Single relay REL-MR- 12DC/1IC 2904475
Plug-in miniature power relay, with power contact for high switch-on currents, 1 N/O contact, input voltage 12 V DC
Classifications
14 mm PLC basic terminal block for high switch-on currents with push-in connection, without relay or solid-state relay, for mounting on DIN rail NS 35/7,5, with load return line connection (BB), 1 N/O contact, input voltage: 12 V DC
14 mm PLC basic terminal block for high switch-on currents with push-in connection, without relay or solid-state relay, for mounting on DIN rail NS 35/7,5, with load return line connection (BB), 1 N/O contact, input voltage: 12 V DC
Plug-in miniature power relay, with power contact for high switch-on currents, 1 N/O contact, input voltage 12 V DC
Plug-in miniature power relay, with power contact for high switch-on currents, 1 N/O contact, input voltage 12 V DC