Key Commercial Data
| Orderkey | 2866019 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 266 (C-5-2017) |
| GTIN | 4017918952662 |
| Weight per Piece (excluding packing) | 139.500 g |
| Custom tariff number | 85364900 |
| Country of origin | AT (Austria) |
Ambient conditions
| Ambient temperature (operation) | -25 °C … 55 °C |
|---|---|
| -25 °C … 40 °C (corresponds to UL 508) | |
| Ambient temperature (storage/transport) | -25 °C … 70 °C |
Input data
| Input current range | 0 mA … 100 mA (Connection terminals: I1 and GND) |
|---|---|
| 0 A … 1 A (Connection terminals: I2 and GND) | |
| 0 A … 10 A (Connection terminals: I3 and GND) | |
| Overload capacity | 800 mA (at IN= 100 mA) |
| 3 A (at IN= 1 A) | |
| 12 A (at IN= 10 A) | |
| Maximum temperature coefficient | < 0.1 %/K |
| Function | Overcurrent |
| Min. setting range | 5 % … 95 % (from IN) |
| Max. setting range | 10 % … 100 % (from IN) |
| Setting range for response delay | 0.2 s … 10 s |
| Basic accuracy | ± 5 % (of scale end value) |
| Setting accuracy | ≤ 5 % (of scale end value) |
| Repeat accuracy | ≤ 2 % |
| Recovery time | 500 ms |
Contact side
| Contact type | 1 floating PDT |
|---|---|
| Maximum switching voltage | 250 V AC (in acc. with IEC 60664-1) |
| Interrupting rating (ohmic load) max. | 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing) |
| 1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing) | |
| Output fuse | 5 A (fast-blow) |
Power supply
| Supply voltage range | 24 V AC … 230 V AC (see Power modules) |
|---|---|
| 24 V DC (see Power modules) |