Key Commercial Data
Orderkey | 2908920 |
---|---|
Packing unit | 1 |
GTIN | 4055626354880 |
Custom tariff number | 85366990 |
Note
Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
---|
General
Nominal voltage UN | < 50 V DC (Per signal/channel) |
---|---|
Max. permissible current | 0.5 A (Signal/channel) |
Supply
Designation | Device supply |
---|---|
Note | Feed-in via MINI MCR-SL-PTB (2864134) power module and MINI MCR-SL-PTB-FM fault signaling module (2902958). |
Input voltage | 24 V DC |
Input voltage range | 19.2 V DC … 30 V DC |
Input current | ≤ 2 A |
Redundant supply | yes, decoupled from diodes |
Polarization and surge protection | Yes |
Output name | Switching output |
Contact type | 1 N/C contact (alarm = open) |
Maximum switching voltage | 30 V DC (2 A) |
Fuse | 2x 2.5 A Slow-blow (exchangeable) |
Status display | 2x green LEDs (PWR1 and PWR2) |
Connection 1
Connection name | Power supply |
---|---|
Connection method | Screw connection |
Stripping length | 7 mm |
Number of connections | 1 |
Number of positions | 6 |
Conductor cross section solid | 0.75 mm² … 2.5 mm² |
Conductor cross section flexible | 0.75 mm² … 2.5 mm² |
Conductor cross section AWG | 18 … 14 |
Connection 2
Connection name | Controller level |
---|---|
Connection in acc. with standard | IEC 60603-2 |
Connection method | Pin strip |
Type | C |
Number of connections | 1 |
Number of positions | 96 |
Ambient conditions
Ambient temperature (operation) | -20 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Permissible humidity (operation) | 5 % … 95 % (non-condensing) |
Shock | 15g, according to IEC 60068-2-27 |
Vibration (operation) | 2g, according to IEC 60068-2-6 |
Standards and Regulations
Designation | Air clearances and creepage distances |
---|---|
Standards/regulations | DIN EN 50178 |
Rated insulation voltage | 30 V |
Rated surge voltage | 0.5 kV |
Insulation | Basic insulation |
Pollution degree | 2 |
Overvoltage category | II |
Designation | Directive 2014/35/EU (EMV) |
Standards/regulations | EN 6100-6-2 |
EN 6100-6-4 | |
Designation | Directive 2014/34/EU (ATEX) |
Standards/regulations | EN 60079-0 |
EN 60079-7 | |
EN 60079-11 | |
Shock | 15g, according to IEC 60068-2-27 |
Vibration (operation) | 2g, according to IEC 60068-2-6 |
ATEX | II 3 G Ex ec IIC T4 Gc X |
UL, USA/Canada | UL 61010 Listed |
Class I, Div. 2, Groups A, B, C, D T4 | |
Class I, Zone 2, Group IIC |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |
Articles in set
Cable set TC-C-MINI-AI-05060708 2902946
Cable set for signal transmission and power supply on the Termination Carrier for modules from the MINI Analog and PSR mini series. Connection of terminal points 5 and 6 (signal transmission) as well as 7 and 8 (power supply) to the signal PCB.
Cable set TC-C-PTB1-AI-SET1 2905217
Cable set for MINI MCR-SL-PTB-FM power module (Order No. 2902958) and MINI MCR-SL-FM-RC-NC error message module (Order No. 2902961), for use on the termination carrier for modules from the MINI Analog series.
Power terminal block MINI MCR-SL-PTB-FM 2902958
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the DIN rail connector. The FM power terminal block offers the additional function of monitoring in combination with the fault monitoring module. Screw connection.
Monitoring module MINI MCR-SL-FM-RC-NC 2902961
The fault monitoring module is used to evaluate and report group errors from the fault monitoring system and to monitor the supply voltages. The error is reported via an N/O contact. Screw connection, standard configuration.
Classifications
[email protected]
[email protected] 4.0 | 27250313 |
---|---|
[email protected] 4.1 | 27250313 |
[email protected] 5.0 | 27250313 |
[email protected] 5.1 | 27250313 |
[email protected] 7.0 | 27141152 |
[email protected] 8.0 | 27141152 |
[email protected] 9.0 | 27141152 |
General
Nominal voltage UN | < 50 V DC (Per signal/channel) |
---|---|
Max. permissible current | 0.5 A (Signal/channel) |
Cable set for signal transmission and power supply on the Termination Carrier for modules from the MINI Analog and PSR mini series. Connection of terminal points 5 and 6 (signal transmission) as well as 7 and 8 (power supply) to the signal PCB.
Cable set for signal transmission and power supply on the Termination Carrier for modules from the MINI Analog and PSR mini series. Connection of terminal points 5 and 6 (signal transmission) as well as 7 and 8 (power supply) to the signal PCB.
Cable set for MINI MCR-SL-PTB-FM power module (Order No. 2902958) and MINI MCR-SL-FM-RC-NC error message module (Order No. 2902961), for use on the termination carrier for modules from the MINI Analog series.
Cable set for MINI MCR-SL-PTB-FM power module (Order No. 2902958) and MINI MCR-SL-FM-RC-NC error message module (Order No. 2902961), for use on the termination carrier for modules from the MINI Analog series.
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the DIN rail connector. The FM power terminal block offers the additional function of monitoring in combination with the fault monitoring module. Screw connection.
The MINI MCR-SL-PTB-FM(-SP) power terminal block is used to supply the supply voltage to the DIN rail connector. The FM power terminal block offers the additional function of monitoring in combination with the fault monitoring module. Screw connection.
The fault monitoring module is used to evaluate and report group errors from the fault monitoring system and to monitor the supply voltages. The error is reported via an N/O contact. Screw connection, standard configuration.
The fault monitoring module is used to evaluate and report group errors from the fault monitoring system and to monitor the supply voltages. The error is reported via an N/O contact. Screw connection, standard configuration.