Ambient conditions
| Ambient temperature (operation) | -40 °C … 85 °C |
|---|---|
| Degree of protection | IP20 (with end cover) |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Standards for cearances and creepage distances | VDE 0110-1 |
| Mounting type | DIN rail: 35 mm |
| Type | Double-level terminal block with PE foot |
| Direction of action | Line-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| D1 | |
| Nominal voltage UN | 30 V DC |
| 110 V AC | |
| Maximum continuous voltage UC | 30 V DC |
| 110 V AC | |
| Rated current | 2 A AC |
| 300 mA DC | |
| Operating effective current IC at UC | ≤ 2 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In (8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp (10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal (8/20) µs | 5 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 650 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 650 V |
| Voltage protection level Up (line-earth) | ≤ 900 V (C2 – 10 kV / 5 kA) |
| Response time tA (line-earth) | ≤ 100 ns |
| Capacity (line-earth) | 2 pF (1 MHz) |
| Surge protection fault message | none |
| Max. required back-up fuse | 2.5 A AC (F) |
| 315 mA DC (F) | |
| Impulse durability (line-earth) | C1 – 1 kV/500 A |
| C2 – 10 kV/5 kA | |
| D1 – 500 A | |
| Alternating current carrying capacity (line-earth) | 2.5 A – 1 s |
Connection data
| Connection method | Spring-cage connection |
|---|---|
| Connection method IN | Spring-cage |
| Connection method OUT | Spring-cage |
| Conductor cross section flexible | 0.5 mm² … 4 mm² |
| Conductor cross section solid | 0.5 mm² … 6 mm² |
| Conductor cross section AWG | 20 … 10 |