Key Commercial Data
| Orderkey | 2801245 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 75 (C-6-2015) |
| GTIN | 4046356766289 |
| Weight per Piece (excluding packing) | 109.100 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 109.3 mm |
|---|---|
| Width | 17.7 mm |
| Depth | 77.5 mm (incl. DIN rail 7.5 mm) |
| Horizontal pitch | 1 Div. |
Ambient conditions
| Ambient temperature (operation) | -40 °C … 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Additional descriptions
| Note | Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector. |
|---|
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 12 V DC |
| Maximum continuous voltage UC | 15 V DC |
| 10 V AC | |
| Rated current | 1000 mA (40 °C) |
| Operating effective current ICat UC | ≤ 1 mA (per path) |
| Residual current IPE | ≤ 1 mA (per path) |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Voltage protection level Up(line-earth) | ≤ 90 V (C1 – 1 kV/500 A) |
| ≤ 135 V (C2 – 10 kV / 5 kA) | |
| ≤ 35 V (C3 – 25 A) | |
| ≤ 35 V (C3 – 50 A) | |
| Voltage protection level Upstatic (line-earth) | ≤ 45 V (C1 – 1 kV/500 A) |
| ≤ 100 V (C2 – 10 kV / 5 kA) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 130 kHz/150 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 600 kHz |
| Capacity (line-signalground) | typ. 4 nF |
| Resistance in series | 1.2 Ω ±5 % |
| Surge protection fault message | Optical, multi-stage |
| Max. required back-up fuse | 1 A (FF) |
| Impulse durability (line-earth) | C1 – 1 kV/500 A |
| C2 – 10 kV/5 kA | |
| C2 – 10 kA | |
| C3 – 50 A | |
| D1 – 2.5 kA | |
| Pulse reset time (line-earth) | ≤ 15 ms |