Key Commercial Data
Orderkey | 2801293 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 146 (C-4-2017) |
GTIN | 4046356766746 |
Weight per Piece (excluding packing) | 121.000 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Dimensions
Height | 109.3 mm |
---|---|
Width | 17.7 mm |
Depth | 77.5 mm (incl. DIN rail 7.5 mm) |
Horizontal pitch | 1 Div. |
Ambient conditions
Ambient temperature (operation) | -40 °C … 70 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Altitude | ≤ 4000 m (amsl (above mean sea level)) |
Degree of protection | IP20 |
General
Housing material | PA 6.6 |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | jet black RAL 9005 |
Standards for cearances and creepage distances | IEC 60664-1 |
Mounting type | DIN rail: 35 mm |
Type | DIN rail module, two-section, divisible |
Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Transmission speed | 90 Mpbs |
Protective circuit
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 12 V DC |
Maximum continuous voltage UC | 15 V DC |
10 V AC | |
Rated current | 600 mA (40 °C) |
Operating effective current ICat UC | ≤ 100 µA (per path) |
Residual current IPE | ≤ 100 µA (per path) |
Nominal discharge current In(8/20) µs (line-line) | 10 kA |
Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
Total discharge current Itotal(8/20) µs | 20 kA |
Voltage protection level Up(line-line) | ≤ 90 V (C1 – 1 kV/500 A) |
≤ 40 V (C3 – 25 A) | |
≤ 40 V (C3 – 50 A) | |
≤ 145 V (C2 – 10 kV / 5 kA) | |
Voltage protection level Up(line-earth) | ≤ 90 V (C1 – 1 kV/500 A) |
≤ 145 V (C2 – 10 kV / 5 kA) | |
≤ 40 V (C3 – 25 A) | |
≤ 40 V (C3 – 50 A) | |
Voltage protection level Upstatic (line-line) | ≤ 55 V (C1 – 1 kV/500 A) |
Voltage protection level Upstatic (line-earth) | ≤ 55 V (C1 – 1 kV/500 A) |
Response time tA(line-line) | ≤ 1 ns |
Response time tA(line-earth) | ≤ 1 ns |
Input attenuation aE, sym. | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
Input attenuation aE, asym. | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 60 MHz |
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system | typ. 60 MHz |
Capacity (line-line) | typ. 30 pF |
Capacity (line-signalground) | typ. 30 pF |
Resistance in series | 1.2 Ω ±5 % |
Surge protection fault message | Optical, multi-stage |
Max. required back-up fuse | 600 mA (FF) |
Impulse durability (line-line) | C1 – 1 kV/500 A |
C2 – 10 kV/5 kA | |
C2 – 10 kA | |
C3 – 25 A | |
C3 – 50 A | |
Impulse durability (line-earth) | C1 – 1 kV/500 A |
C2 – 10 kV/5 kA | |
C2 – 10 kA | |
C3 – 25 A | |
C3 – 50 A | |
D1 – 2.5 kA | |
Impulse durability (line-signalground) | C1 – 1 kV/500 A |
C2 – 10 kV/5 kA | |
C2 – 10 kA | |
C3 – 25 A | |
C3 – 50 A | |
Pulse reset time (line-line) | ≤ 15 ms |
Pulse reset time (line-signalground) | ≤ 15 ms |
Connection data
Connection method | Push-in connection |
---|---|
Stripping length | 10 mm |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section solid | 0.2 mm² … 4 mm² |
Conductor cross section AWG | 24 … 12 |