Key Commercial Data
Orderkey | 2880561 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 180 (C-4-2017) |
GTIN | 4046356048941 |
Weight per Piece (excluding packing) | 228.240 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -25 °C … 55 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 80 °C |
Altitude | ≤ 4000 m (amsl (above mean sea level)) |
Degree of protection | IP40 |
General
Housing material | Zinc die-cast |
---|---|
Color | silver |
Standards for cearances and creepage distances | IEC 60664-1 |
DIN VDE 0110-1 | |
Overvoltage category | II |
Degree of pollution | 2 |
Mounting type | Screw mounting |
Type | Housing for surface mounting |
Number of positions | 5 |
Direction of action | Line-Shield/Earth Ground |
Protective circuit
IEC test classification | B2 |
---|---|
C1 | |
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 14 V DC (vertical) |
18 V DC (horizontal) | |
Maximum continuous voltage UC | 20 V DC |
Rated current | 400 mA |
Operating effective current ICat UC | ≤ 2 µA (per channel) |
Residual current IPE | ≤ 2 µA (per channel) |
Nominal discharge current In(8/20) µs (line-shield) | 2.5 kA |
Total discharge current Itotal(8/20) µs | 10 kA |
Max. discharge current Imax(8/20) µs maximum (line-shield) | 2.5 kA |
Nominal pulse current Ian (10/1000) µs (Core-Shield) | 100 A |
Nominal pulse current Ian (10/700) µs (Core-Shield) | 100 A |
Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 80 V |
Voltage protection level Up(line-shield) | ≤ 500 V (C2 – 4 kV / 2 kA) |
≤ 120 V (C3 – 100 A) | |
Response time tA (line-shield) | ≤ 1 ns |
Input attenuation aE, asym. | ≤ 1 dB (5 MHz … 2,2 GHz / 75 Ω) |
≤ 3 dB (5 MHz … 2,4 GHz / 75 Ω) | |
Near-end crosstalk attenuation | ≥ 40 dB (5 MHz … 2,4 GHz / 75 Ω) |
Cut-off frequency fg (3 dB), asym. (shield) in 75 Ohm system | > 2.5 GHz |
Frequency range | 47 MHz … 2.5 GHz |
Inductivity in series | typ. 5 µH (f = 10 kHz) |
Resistance in series | 3.3 Ω ±20 % |
Surge protection fault message | none |
Impulse durability (line-shield) | B2 – 4 kV/100 A |
C1 – 1 kV/500 A | |
C2 – 4 kV/2 kA | |
C3 – 100 A | |
D1 – 500 A | |
Impulse durability (shield-earth) | C2 – 10 kA |
D1 – 5 kA |
Connection data
Connection method | F connector |
---|---|
Connection method IN | F connector, female |
Connection method OUT | F connector, female |