Key Commercial Data
Orderkey | 1064665 |
---|---|
Packing unit | 1 |
Catalog page | Page 158 (C-4-2019) |
GTIN | 4055626722733 |
Custom tariff number | 85363010 |
Ambient conditions
Ambient temperature (operation) | -40 °C … 85 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Permissible humidity (operation) | 5 % … 95 % |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Degree of protection | IP20 |
General
Housing material | PBT |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | sky blue RAL 5015 |
Mounting type | DIN rail: TH 35 – 7.5 mm |
Type | DIN rail module, two-section, divisible |
Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 30 V DC |
Rated current | 5 A (55 °C) |
Operating effective current ICat UC | ≤ 5 µA |
Residual current IPE | ≤ 1 µA |
Nominal discharge current In(8/20) µs (line-line) | 0.5 kA |
Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
Total discharge current Itotal(8/20) µs | 10 kA |
Voltage protection level Up(line-line) | ≤ 68 V (C1 – 1 kV/500 A) |
≤ 50 V (C3 – 100 A) | |
≤ 50 V (C3 – 25 A) | |
Voltage protection level Up(line-earth) | ≤ 700 V (C1 – 1 kV/500 A) |
≤ 900 V (C2 – 10 kV / 5 kA) | |
Response time tA(line-line) | ≤ 1 ns |
Response time tA(line-earth) | ≤ 100 ns |
Input attenuation aE, sym. | typ. 0.3 dB (≤ 12 MHz / 150 Ω) |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 60 MHz |
Capacity (line-line) | typ. 30 pF |
Capacity (line-earth) | typ. 30 pF |
Resistance per path | < 0.1 Ω |
Max. required back-up fuse | 5 A (F) |
Impulse durability (line-line) | C1 – 1 kV / 500 A |
C3 – 100 A | |
Impulse durability (line-earth) | C1 – 1 kV / 500 A |
C2 – 10 kV / 5 kA | |
D1 – 500 A | |
Pulse reset time (line-line) | ≤ 30 ms |
Pulse reset time (line-earth) | ≤ 500 ms |
Connection data
Connection method | Screw connection |
---|---|
Screw thread | M3 |
Tightening torque | 0.5 Nm … 0.6 Nm |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
Conductor cross section solid | 0.2 mm² … 4 mm² |
Conductor cross section AWG | 24 … 12 |
Standards and Regulations
Standards/specifications | EN 60079-0 2012 + A11:2013 |
---|---|
EN 60079-11 2012 | |
EN 61643-21 2001 + A1:2009 + A2:2013 | |
IEC 60079-0 2011 (modified) + corrigendum 2012 + corrigendum 2013 | |
IEC 60079-11 2008 | |
IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
General
Maximum inner capacitance Ci | negligible |
---|---|
Max. internal inductance Li | negligible |
Max. input current Ii | 400 mA (T4 / ≤ 50 °C) |
350 mA (T6 / ≤ 35 °C) | |
Max. input voltage Ui | 30 V DC |
Ambient temperature (operation) | -40 °C … 35 °C (T6 / 85 °C) |
-40 °C … 50 °C (T4 / 135 °C) |
Environmental Product Compliance
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |