Ambient conditions
Ambient temperature (operation) | -20 °C … 55 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Input data
Rated control circuit supply voltage US | 120 V AC/DC -20 % … +10 % |
---|---|
Rated control supply current IS | typ. 11 mA |
Power consumption at US | typ. 1.32 W |
Inrush current | typ. 600 mA (Δt = 200 µs at Us) |
Typ. starting time with Us | typ. 20 ms (when controlled via A1) |
Typical release time | typ. 20 ms (when controlled via A1) |
Recovery time | < 500 ms |
Operating voltage display | 1 x green LED |
Protective circuit | Surge protection Varistor |
Maximum switching frequency | 0.5 Hz |
Output data
Contact type | 5 enabling current paths |
---|---|
2 confirmation current paths | |
Contact material | AgSnO2 |
Maximum switching voltage | 230 V AC/DC (Observe the load curve) |
Minimum switching voltage | 5 V AC/DC |
Limiting continuous current | 6 A (N/O contact) |
3 A (N/C contact) | |
Maximum inrush current | 6 A |
Inrush current, minimum | 10 mA |
Sq. Total current | 72 A2 |
Interrupting rating (ohmic load) max. | 144 W (N/O contact, 24 V DC, τ = 0 ms) |
288 W (N/O contact, 48 V DC, τ = 0 ms) | |
240 W (N/O contact, 60 V DC, τ = 0 ms) | |
110 W (N/O contact, 110 V DC, τ = 0 ms) | |
88 W (N/O contact, 220 V DC, τ = 0 ms) | |
1380 VA (N/O contact, 230 V AC, τ = 0 ms) | |
Maximum interrupting rating (inductive load) | 42 W (N/O contact, 24 V DC, τ = 40 ms) |
42 W (N/O contact, 48 V DC, τ = 40 ms) | |
42 W (N/O contact, 60 V DC, τ = 40 ms) | |
42 W (N/O contact, 110 V DC, τ = 40 ms) | |
42 W (N/O contact, 220 V DC, τ = 40 ms) | |
Switching capacity | min. 50 mW |
Mechanical service life | 10x 106 cycles |
Switching capacity (360/h cycles) | 4 A (24 V (DC13)) |
4 A (250 V (AC15)) | |
Switching capacity according to IEC 60947-5-1 | 3 A (24 V (DC13)) |
3 A (250 V (AC15)) | |
Output fuse | 10 A gL/gG (N/O contact) |
4 A gL/gG (N/O contact, for low-demand applications) | |
6 A gL/gG (N/C contact) |
General
Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
---|---|
Nominal operating mode | 100% operating factor |
Net weight | 135.88 g |
Mounting position | vertical or horizontal |
Mounting type | DIN rail mounting |
Degree of protection | IP20 |
IP54 | |
Min. degree of protection of inst. location | IP54 |
Housing material | PBT |
Housing color | yellow |