Key Commercial Data
Orderkey | 2807939 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 107 (C-6-2013) |
GTIN | 4017918075415 |
Weight per Piece (excluding packing) | 1.330 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
General
Housing material | PBT |
---|---|
Flammability rating according to UL 94 | V0 |
Color | black |
Standards for cearances and creepage distances | VDE 0110-1 |
Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
Type | LSA-PLUS module |
Direction of action | Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Protective circuit
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 40 V DC |
28 V AC | |
Rated current | 140 mA (25 °C) |
Operating effective current ICat UC | ≤ 5 µA (18x) |
Residual current IPE | ≤ 1 µA |
Nominal discharge current In(8/20) µs (line-line) | 5 kA |
Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
Total discharge current Itotal(8/20) µs | 10 kA |
Max. discharge current Imax(8/20) µs | 5 kA |
Max. discharge current Imax(8/20) µs maximum (line-earth) | |
Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 60 V (a, b) |
Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 650 V |
Residual voltage at In(line-line) | ≤ 85 V (a-b) |
Residual voltage at In(line-signalground) | ≤ 85 V |
Response time tA(line-line) | ≤ 1 ns (a-b) |
Response time tA(line-earth) | ≤ 100 ns (a, b) |
Input attenuation aE, sym. | 1.8 dB (Typ. up to 1 MHz / 50 Ω) |
0.6 dB (Typ. up to 400 kHz / 150 Ω) | |
0.2 dB (Typ. up to 60 kHz / 600 Ω) | |
Input attenuation aE, asym. | |
Cut-off frequency fg (3 dB), sym. in 50 Ohm system | 6 MHz (typ.) |
Cut-off frequency fg (3 dB), sym. in 150 Ohm system | 2.5 MHz (typ.) |
Cut-off frequency fg (3 dB), sym. in 600 Ohm system | 750 kHz (typ.) |
Capacity (line-earth) | 1.1 nF (1 MHz a … b) |
Resistance in series | 22 Ω ±10 % |
Surge protection fault message | none |
Max. required back-up fuse | 145 mA |
Impulse durability (line-earth) | D1 – 2.5 kA |
Impulse durability (signalground-earth) | D1 – 2.5 kA |
Connection data
Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
---|---|
Connection method IN | COMTRAB plug-in system |
Connection method OUT | COMTRAB plug-in system |