Key Commercial Data
| Orderkey | 2906281 |
|---|---|
| Packing unit | 12 pc |
| Minimum order quantity | 12 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 39 (C-4-2017) |
| GTIN | 4055626063065 |
| Weight per Piece (excluding packing) | 149.000 g |
| Custom tariff number | 85363090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C … 80 °C |
| Ambient temperature (storage/transport) | -40 °C … 80 °C |
| Altitude | max. 2000 m |
| Permissible humidity (operation) | 5 % … 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 … 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | I / II |
|---|---|
| T1 / T2 | |
| I | |
| EN type | T1 / T2 |
| IEC power supply system | DC |
| Mode of protection | L-PEN |
| (L+) – (L-) | |
| (L-) – PE | |
| (L+) – PE | |
| Mounting type | DIN rail: 35 mm |
| Color | black |
| Housing material | PBT |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 1 |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | -48 V DC (RRH) |
|---|---|
| 60 V DC | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 75 V AC |
| 100 V DC | |
| Maximum continuous operating voltage UC(L-PEN) | 75 V AC |
| 100 V DC | |
| 75 V AC | |
| 100 V DC | |
| Rated load current IL | 80 A |
| 80 A | |
| Residual current IPE | ≤ 0.6 mA |
| ≤ 0.6 mA | |
| Standby power consumption PC | ≤ 45 mVA |
| ≤ 45 mVA | |
| Nominal discharge current In(8/20) µs | 12.5 kA |
| Maximum discharge current Imax(8/20) µs | 30 kA |
| 30 kA | |
| Maximum discharge current Imax(8/20) µs (L-N) | 30 kA |
| Maximum discharge current Imax(8/20) µs (L-PEN) | 30 kA |
| Impulse discharge current (10/350) µs, charge | 6.25 As |
| Impulse discharge current (10/350) µs, specific energy | 39 kJ/Ω |
| Impulse discharge current (10/350) µs, peak value limp | 12.5 kA |
| 12.5 kA | |
| Impulse discharge current (10/350) µs (L-N), charge | 6.25 As |
| 6.25 As | |
| Impulse discharge current (10/350) µs (L-N), specific energy | 39 kJ/Ω |
| 39 kJ/Ω | |
| Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 12.5 kA |
| 12.5 kA | |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 0.4 kV |
| Voltage protection level Up(L-N) | ≤ 0.4 kV |
| Voltage protection level Up(L-PEN) | ≤ 0.4 kV |
| Residual voltage Ures | ≤ 0.4 kV (at In) |
| ≤ 0.35 kV (at 10 kA) | |
| ≤ 0.3 kV (at 5 kA) | |
| ≤ 0.275 kV (at 4 kA) | |
| ≤ 0.25 kV (at 3 kA) | |
| TOV behavior at UT | 100 V AC (5 s / withstand mode) |
| 130 V DC (5 s / withstand mode) | |
| Response time tA | ≤ 25 ns |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PEN) | ≤ 25 ns |
| Max. backup fuse with V-type through wiring | 80 A AC (gG – 16 mm²) |
| 80 A AC (gG – 16 mm²) | |
| Max. backup fuse with branch wiring | 160 A AC (gG) |
| 160 A AC (gG) |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 4.5 Nm |
| 30 lbf-in. (UL) | |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² … 25 mm² |
| Conductor cross section solid | 1.5 mm² … 35 mm² |
| Conductor cross section AWG | 15 … 2 |
| 10 … 2 (UL) |