Key Commercial Data
| Orderkey | 1020304 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 12 (C-6-2019) |
| GTIN | 4055626510088 |
| Weight per Piece (excluding packing) | 120.000 g |
| Custom tariff number | 85389099 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer’s declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -25 °C … 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Permissible humidity (operation) | 10 % … 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % … 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa … 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 10 kPa … 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Connection data
| Designation | Inline connector |
|---|---|
| Connection method | Spring-cage connection |
| Conductor cross section solid min. | 0.08 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.08 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 28 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
General
| Mounting type | DIN rail mounting |
|---|---|
| Net weight | 66 g |
| Diagnostics messages | Bus error in INTERBUS Yes |
| Peripheral fault in INTERBUS Yes | |
| Mounting type | DIN rail mounting |
Inline potentials
| Designation | 24 V supply UILC |
|---|---|
| Supply voltage | 24 V DC -15 % / +20 % (acc. to EN 61131-2) |
| Current consumption | 20 mA |
| Designation | 7.5 V communications power UL(potential jumper) |
| Supply voltage | 7.5 V DC ±5 % |
| Power supply unit | max. 0.8 A DC (observe derating) |
| Designation | 24 V analog supply UANA(potential jumper) |
| Supply voltage | 24 V DC -15 % / +20 % |
| Supply voltage range | 19.2 V DC … 30 V DC (including all tolerances, including ripple) |
| Power supply unit | 0.5 A DC (observe derating) |
| Designation | 24 V main supply UM |
| Supply voltage | 24 V DC -15 % / +20 % (acc. to EN 61131-2) |
| Supply voltage range | 19.2 V DC … 30 V DC (including all tolerances, including ripple) |
| Power supply unit | max. 8 A DC (sum of UM+ US) |
| Designation | 24 V segment supply US |
| Supply voltage | 24 V DC -15 % / +20 % (in accordance with EN 61131) |
| Supply voltage range | 19.2 V DC … 30 V DC (including all tolerances, including ripple) |
| Power supply unit | max. 8 A (sum of UM+ US) |
| Type of protection | Polarity reversal protection of the supply voltage |
| Transient protection |
Standards and Regulations
| Mechanical tests | Shock in acc. with EN 60068-2-27/IEC 60068-2-27 30g, 11 ms period, half-sine shock pulse |
|---|---|
| Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g | |
| Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g |
Environmental Product Compliance
| REACh SVHC | |
|---|---|
| Lead 7439-92-1 | |
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |
Classifications
[email protected]
| [email protected] 6.0 | 27242600 |
|---|---|
| [email protected] 7.0 | 27242608 |
| [email protected] 8.0 | 27242608 |
| [email protected] 9.0 | 27242608 |