Key Commercial Data
Orderkey | 2702171 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 300 (C-6-2017) |
GTIN | 4055626004983 |
Weight per Piece (excluding packing) | 222.000 g |
Custom tariff number | 85389091 |
Country of origin | DE (Germany) |
Dimensions
Dimensional drawing | |
---|---|
Width | 53.6 mm |
Height | 126.1 mm |
Depth | 54 mm |
Note on dimensions | Housing dimensions |
Ambient conditions
Ambient temperature (operation) | -35 °C … 60 °C (Mounting position: any) |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Permissible humidity (operation) | 10 % … 75 % (on average, 85% infrequently, non-condensing) |
Permissible humidity (storage/transport) | 10 % … 75 % (non-condensing) |
Air pressure (operation) | 70 kPa … 108 kPa (up to 3000 m above sea level) |
Air pressure (storage/transport) | 66 kPa … 108 kPa (up to 3500 m above sea level) |
Degree of protection | IP20 |
Digital outputs
Output name | Digital outputs |
---|---|
Connection method | Direct plug-in technology |
Connection technology | 2, 3-wire |
Number of outputs | 4 (with two-channel assignment) |
8 | |
Type of protection | Overload protection, freewheeling circuit for inductive loads, Discharge circuit for accelerated discharge of capacitive loads |
Output voltage | 24 V DC |
Output current | max. 2 A (per channel) |
max. 1.5 A (per channel according to CULUS) | |
max. 4 A (per group) | |
max. 3 A (per group according to CULUS) | |
max. 8 A (Total current of all outputs; Please observe the notes in the user manual.) | |
max. 6 A (Total current of all outputs according to CULUS) | |
Maximum output current per channel | 2 A |
Maximum output current per module / terminal block | 8 A |
General
Mounting type | DIN rail |
---|---|
Net weight | 222 g |
Note on weight specifications | with connectors and bus base module |