Key Commercial Data
Orderkey | 3212081 |
---|---|
Packing unit | 10 pc |
Minimum order quantity | 10 pc |
Catalog page | Page 125 (C-1-2017) |
GTIN | 4046356869843 |
Weight per Piece (excluding packing) | 83.540 g |
Custom tariff number | 85369010 |
Country of origin | PL (Poland) |
General
Number of positions | 1 |
---|---|
Number of levels | 1 |
Number of connections | 2 |
Potentials | 1 |
Nominal cross section | 35 mm² |
Color | black/yellow |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 8 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation for nominal condition | 4.06 W |
Maximum load current | 125 A (with 35 mm² conductor cross section) |
Nominal current IN | 125 A |
Nominal voltage UN | 1000 V |
Open side panel | No |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Connection data
Connection method | Power-Turn connection |
---|---|
Conductor cross section solid min. | 2.5 mm² |
Conductor cross section solid max. | 35 mm² |
Conductor cross section AWG min. | 12 |
Conductor cross section AWG max. | 2 |
Conductor cross section flexible min. | 2.5 mm² |
Conductor cross section flexible max. | 35 mm² |
Min. AWG conductor cross section, flexible | 12 |
Max. AWG conductor cross section, flexible | 2 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 2.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 35 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 2.5 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 35 mm² |
Stripping length | 25 mm |
Standards and Regulations
Flammability rating according to UL 94 | V0 |
---|---|
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Environmental Product Compliance
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |