Key Commercial Data
Orderkey | 2906031 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 316 (C-4-2017) |
GTIN | 4055626149349 |
Weight per Piece (excluding packing) | 119.700 g |
Custom tariff number | 85363090 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -25 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 70 °C |
Humidity test | 96 h, 95 % RH, 40 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Shock (operation) | 30g (IEC 60068-2-27, Test Ea) |
Vibration (operation) | 10 Hz … 57.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc) |
57.6 Hz … 150 Hz (Acceleration 5g; in accordance with IEC 60068-2-6, Test Fc) | |
Degree of protection | IP20 |
General
Flammability rating according to UL 94 | V-0 |
---|---|
Mounting type | DIN rail: 35 mm |
Color | light grey RAL 7035 |
Number of positions | 4 |
Protection class | III |
Type | DIN rail module, one-piece |
Electrical data
Fuse type | electronic |
---|---|
Rated surge voltage | 0.5 kV |
Operating voltage | 18 V DC … 30 V DC |
Rated voltage | 24 V DC |
Rated current IN | max. 16 A DC (IN+) |
max. 40 A DC (per terminal position when bridging additional devices via IN+) | |
Measuring tolerance I | ± 15 % |
Feedback resistance | max. 35 V DC |
Fail-safe element | 4 A DC (per output channel) |
Efficiency | > 99 % |
Closed circuit current I0 | typ. 33 mA |
Power dissipation | typ. 0.8 W (No-load operation) |
< 4 W (Nominal operation) | |
Module initialization time | 1.6 s |
Waiting time after switch off of a channel | 5 s (at overload / short circuit) |
Tripping method | E (electronic) |
Required backup fuse | not required, integrated failsafe element |
Dielectric strength | max. 35 V DC (Load circuit) |
MTBF (IEC 61709, SN 29500) | 11764705 h (at 25°C with 21% load) |
5319148 h (at 40°C with 34.25% load) | |
846023 h (at 60°C with 100% load) | |
Shutdown time load circuit | ≤ 10 ms (for short circuit > 2.0 x IN) |
1 s (1.2 … 2.0 x IN) | |
Undervoltage shutdown load circuit | ≤ 17.8 V DC (active) |
≥ 18.8 V DC (inactive) | |
Surge voltage shutdown load circuit | ≥ 30.5 V DC (active) |
≤ 29.5 V DC (inactive) | |
Max. capacitive load load circuit | 30000 µF (Depending on the current setting and the short-circuit current available) |
Remote indication contact
Connection name | Remote indication circuit |
---|---|
Switching function | N/O contact |
Stripping length | 10 mm |
Conductor cross section solid | 0.2 mm² … 2.5 mm² |
Conductor cross section AWG | 24 … 12 |
Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² … 1.5 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² … 2.5 mm² |
DC operating voltage | 0 V DC … 30 V DC |
DC operating current | 100 mA DC |