Key Commercial Data
Orderkey | 2902992 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 226 (C-4-2017) |
GTIN | 4046356729208 |
Weight per Piece (excluding packing) | 242.300 g |
Custom tariff number | 85044030 |
Country of origin | PL (Poland) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 55 °C Derating: 2.5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Input data
Nominal input voltage range | 100 V AC … 240 V AC |
---|---|
Input voltage range | 85 V AC … 264 V AC |
Current consumption | 1.3 A (100 V AC) |
0.6 A (240 V AC) | |
Nominal power consumption | 135.5 VA |
Inrush surge current | < 30 A (typical) |
Mains buffering | typ. 20 ms (120 V AC) |
typ. 85 ms (230 V AC) | |
Input fuse | 2.5 A (slow-blow, internal) |
Choice of suitable circuit breakers | 6 A … 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) | 0.49 |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Output data
Nominal output voltage | 24 V DC ±1 % |
---|---|
Nominal output current (IN) | 2.5 A (-25 °C … 55 °C) |
Derating | 55 °C … 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback resistance | < 35 V DC |
Output overvoltage protection | ≤ 35 V DC |
Control deviation | < 1 % (change in load, static 10 % … 90 %) |
< 2 % (Dynamic load change 10 % … 90 %, 10 Hz) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 30 mVPP(with nominal values) |
Output power | 60 W |
Typical response time | < 1 s |
Maximum power dissipation in no-load condition | < 0.3 W |
Power loss nominal load max. | < 7 W |
General
Net weight | 0.2 kg |
---|---|
Efficiency | typ. 88 % (120 V AC) |
typ. 90 % (230 V AC) | |
Insulation voltage input/output | 4 kV AC (type test) |
3 kV AC (routine test) | |
Protection class | II (in closed control cabinet) |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 785000 h (40 °C) |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: 0 mm horizontally, 30 mm vertically |