Key Commercial Data
Orderkey | 2866459 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 177 (C-6-2013) |
GTIN | 4046356046701 |
Weight per Piece (excluding packing) | 1,300.000 g |
Custom tariff number | 85044030 |
Country of origin | CN (China) |
Ambient conditions
Degree of protection | IP20 |
---|---|
Ambient temperature (operation) | -25 °C … 70 °C (> 55° C derating : 2.5%/K) |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Input data
Nominal input voltage range | 2x / 3x 400 V AC … 500 V AC |
---|---|
Input voltage range | 3x 320 V AC … 575 V AC |
2x 360 V AC … 575 V AC (for 2-phase operation) | |
AC frequency range | 45 Hz … 65 Hz |
Discharge current to PE | < 3.5 mA |
Current consumption | 3x 0.6 A (400 V AC) |
3x 0.5 A (480 V AC) | |
Nominal power consumption | 456 VA |
Inrush surge current | < 15 A |
Mains buffering | > 20 ms (3x 400 V AC) |
Input fuse | < |
Choice of suitable circuit breakers | < 6 A … 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) | 0.59 |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Maximum input current | < |
Nominal input current | < |
Maximum input current | < |
Output data
Nominal output voltage | 24 V DC ±1 % |
---|---|
Setting range of the output voltage (USet) | 22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) | 10 A (UOUT= 24 V DC) |
Derating | 55 °C … 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback resistance | 35 V DC |
Output overvoltage protection | < 35 V DC |
Max. capacitive load | unlimited |
Active current limitation | approx. 15 A |
Control deviation | < 1 % (change in load, static 10 % … 90 %) |
< 2 % (change in load, dynamic 10 % … 90 %) | |
< 0.1 % (change in input voltage ±10 %) | |
Residual ripple | < 10 mVPP |
Output power | 240 W |
Typical response time | < 1 s |
Peak switching voltages nominal load | < 30 mVPP |
Maximum power dissipation in no-load condition | 7.5 W |
Power loss nominal load max. | 34 W |
General
Net weight | 1.1 kg |
---|---|
Operating voltage display | Green LED |
Efficiency | 88.5 % (at 400 V AC and nominal values) |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage input / PE | 2 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage output / PE | 500 V DC (routine test) |
Protection class | I (with PE connection) |
Degree of protection | IP20 |
MTBF (IEC 61709, SN 29500) | > 1156000 h |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: horizontally 0 mm, vertically 50 mm |