Key Commercial Data
Orderkey | 2905908 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 282 (C-4-2017) |
GTIN | 4055626007397 |
Weight per Piece (excluding packing) | 6,098.000 g |
Custom tariff number | 85044030 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | 0 °C … 40 °C |
---|---|
Ambient temperature (storage/transport) | -15 °C … 40 °C (with charged energy storage device) |
Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
Maximum altitude | ≤ 3000 mm (> 2000 m, observe derating) |
Vibration (operation) | 5 Hz … 100 Hz, 0.7g (EN 60068-2-6) |
Shock | 20g in all directions (EN 60068-2-27) |
30g in each space direction with UWA 130 | |
Degree of pollution | 2 |
Climatic class | 3K3 (in acc. with EN 60721) |
Input data
Nominal input voltage | 120 V AC |
---|---|
Input voltage range | 96 V AC … 138 V AC |
Frequency range | 55 Hz … 65 Hz |
Current consumption | 6 A |
Permissible backup fuse | B10 B16 Listed breaker |
Connection data, input
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 4 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 10 mm |
Output data
Apparent power | 750 VA |
---|---|
Rated Power (Real Power) | 600 W |
Power factor (cos phi) | 0.8 |
Crest factor | 2.8 |
Switch-over time | < 10 ms |
Classification according to IEC 62040-3 | VFD-SS-311 |