Key Commercial Data
Orderkey | 3038875 |
---|---|
Packing unit | 50 pc |
Catalog page | Page 178 (C-1-2017) |
GTIN | 4017918941246 |
Weight per Piece (excluding packing) | 10.670 g |
Custom tariff number | 85369010 |
Country of origin | TR (Turkey) |
General
Number of levels | 1 |
---|---|
Number of connections | 2 |
Nominal cross section | 4 mm² |
Color | gray |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Area of application | Railway industry |
Machine building | |
Plant engineering | |
Rated surge voltage | 6 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Connection in acc. with standard | IEC 60947-7-1 |
Nominal current IN | 20 A (with 6 mm² conductor cross section) |
Maximum load current | 20 A (with 6 mm² conductor cross section) |
Nominal voltage UN | 400 V |
Open side panel | No |
Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
Back of the hand protection | guaranteed |
Finger protection | guaranteed |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 7.3 kV |
Result of power-frequency withstand voltage test | Test passed |
Power frequency withstand voltage setpoint | 1.89 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of bending test | Test passed |
Bending test rotation speed | 10 rpm |
Bending test turns | 135 |
Bending test conductor cross section/weight | 0.08 mm² / 0.1 kg |
4 mm² / 0.9 kg | |
6 mm2/ 1.4 kg | |
Tensile test result | Test passed |
Conductor cross section tensile test | 0.08 mm² |
Tractive force setpoint | 5 N |
Conductor cross section tensile test | 4 mm² |
Tractive force setpoint | 60 N |
Conductor cross section tensile test | 6 mm² |
Tractive force setpoint | 80 N |
Result of tight fit on support | Test passed |
Tight fit on carrier | NS 35 |
Setpoint | 1 N |
Result of voltage-drop test | Test passed |
Result of temperature-rise test | Test passed |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 2.5 mm² |
Short-time current | 0.3 kA |
Result of aging test | Test passed |
Ageing test for screwless modular terminal block temperature cycles | 192 |
Result of thermal test | Test passed |
Proof of thermal characteristics (needle flame) effective duration | 30 s |
Oscillation, broadband noise test result | Test passed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum | Service life test category 2, bogie-mounted |
Test frequency | f1= 5 Hz to f2= 250 Hz |
ASD level | 6.12 (m/s2)2/Hz |
Acceleration | 3.12 g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock test result | Test passed |
Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form | Half-sine |
Acceleration | 30g |
Shock duration | 18 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Connection data
Conductor cross section solid min. | 0.08 mm² |
---|---|
Conductor cross section solid max. | 6 mm² |
Conductor cross section flexible min. | 0.08 mm² |
Conductor cross section flexible max. | 4 mm² |
Conductor cross section AWG min. | 28 |
Conductor cross section AWG max. | 10 |
Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 1 mm² |
Connection method | Spring-cage connection |
Stripping length | 8 mm … 10 mm |
Internal cylindrical gage | A4 |
Standards and Regulations
Connection in acc. with standard | CSA |
---|---|
IEC 60947-7-1 | |
Flammability rating according to UL 94 | V0 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Environmental Product Compliance
China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
---|---|
No hazardous substances above threshold values |