Key Commercial Data
| Orderkey | 2130172 |
|---|---|
| Packing unit | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 555 (C-1-2017) |
| GTIN | 4017918052959 |
| Weight per Piece (excluding packing) | 305.500 g |
| Custom tariff number | 85369010 |
| Country of origin | IN (India) |
General
| Number of levels | 1 |
|---|---|
| Number of connections | 2 |
| Nominal cross section | 95 mm² |
| Color | gray |
| Insulating material | PA-F |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | II |
| Maximum power dissipation for nominal condition | 7.54 W |
| Connection in acc. with standard | IEC 60947-7-1 |
| Nominal current IN | 232 A |
| Maximum load current | 232 A (with 95 mm2conductor cross section) |
| Nominal voltage UN | 1000 V |
| Open side panel | No |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 2.2 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 25 mm² / 4.5 kg |
| 35 mm² / 6.8 kg | |
| 95 mm²/14 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 25 mm² |
| Tractive force setpoint | 135 N |
| Conductor cross section tensile test | 35 mm² |
| Tractive force setpoint | 190 N |
| Conductor cross section tensile test | 95 mm² |
| Tractive force setpoint | 351 N |
| Result of tight fit on support | Test passed |
| Setpoint | 15 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 95 mm² |
| Short-time current | 11.4 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Relative insulation material temperature index (Elec., UL 746 B) | 120 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Connection data
| Connection method | Screw connection |
|---|---|
| Conductor cross section solid min. | 25 mm² |
| Conductor cross section solid max. | 95 mm² |
| Conductor cross section flexible min. | 35 mm² |
| Conductor cross section flexible max. | 95 mm² |
| Conductor cross section AWG min. | 3 |
| Conductor cross section AWG max. | 3/0 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 35 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 95 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 35 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 95 mm² |
| 2 conductors with same cross section, solid min. | 25 mm² |
| 2 conductors with same cross section, solid max. | 35 mm² |
| 2 conductors with same cross section, stranded min. | 25 mm² |
| 2 conductors with same cross section, stranded max. | 35 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 16 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 35 mm² |
| Stripping length | 29 mm |
| Screw thread | M8 |
| Tightening torque, min | 15 Nm |
| Tightening torque max | 20 Nm |
| Power rail | 30 mm x 5 mm |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |