Key Commercial Data
Orderkey | 3049563 |
---|---|
Packing unit | 10 pc |
Minimum order quantity | 10 pc |
Catalog page | Page 551 (C-1-2017) |
GTIN | 4046356310314 |
Weight per Piece (excluding packing) | 222.230 g |
Custom tariff number | 39269097 |
Country of origin | DE (Germany) |
General
Number of levels | 1 |
---|---|
Number of connections | 2 |
Nominal cross section | 120 mm² |
Color | gray |
Insulating material | PA |
Flammability rating according to UL 94 | V0 |
Rated surge voltage | 8 kV |
Degree of pollution | 3 |
Overvoltage category | III |
Insulating material group | I |
Maximum power dissipation for nominal condition | 8.68 W |
Connection in acc. with standard | IEC 60947-7-1 |
Nominal current IN | 269 A |
Maximum load current | 269 A |
Nominal voltage UN | 1000 V |
Open side panel | No |
Result of surge voltage test | Test passed |
Surge voltage test setpoint | 9.8 kV |
Result of power-frequency withstand voltage test | Test passed |
Power frequency withstand voltage setpoint | 2.2 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
Result of tight fit on support | Test passed |
Tight fit on carrier | NS 35 |
Setpoint | 15 N |
Result of voltage-drop test | Test passed |
Requirements, voltage drop | ≤ 3.2 mV |
Result of temperature-rise test | Test passed |
Short circuit stability result | Test passed |
Conductor cross section short circuit testing | 120 mm² |
Short-time current | 14.4 kA |
Result of thermal test | Test passed |
Proof of thermal characteristics (needle flame) effective duration | 10 s |
Oscillation, broadband noise test result | Test passed |
Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
Test spectrum | Service life test category 1, class B, body mounted |
Test frequency | f1= 5 Hz to f2= 150 Hz |
ASD level | 0.02 g²/Hz |
Acceleration | 0,8 g |
Test duration per axis | 5 h |
Test directions | X-, Y- and Z-axis |
Shock test result | Test passed |
Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
Shock form | Half-sine |
Acceleration | 5 g |
Shock duration | 30 ms |
Number of shocks per direction | 3 |
Test directions | X-, Y- and Z-axis (pos. and neg.) |
Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Static insulating material application in cold | -60 °C |
Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
Flame test method (DIN EN 60695-11-10) | V0 |
Oxygen index (DIN EN ISO 4589-2) | >32 % |
NF F16-101, NF F10-102 Class I | 2 |
NF F16-101, NF F10-102 Class F | 2 |
Surface flammability NFPA 130 (ASTM E 162) | passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Dimensions
Length | 67 mm |
---|---|
Width | 32 mm |
Height | 73.5 mm |
Height NS 35/7,5 | 76 mm |
Height NS 35/15 | 83.5 mm |
Bolt length | 26 mm |
Connection data
Connection method | Bolt connection |
---|---|
Conductor cross section solid min. | 6 mm² |
Conductor cross section solid max. | 120 mm² |
Conductor cross section flexible min. | 6 mm² |
Conductor cross section flexible max. | 120 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. | 6 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. | 120 mm² |
Cable lug connection according to standard | DIN 46234 |
Min. cross section for cable lug connection | 6 mm² |
Max. cross section for cable lug connection | 120 mm² |
Bolt length | 26 mm |
Bolt diameter | 10 mm |
Tightening torque, min | 10 Nm |
Tightening torque max | 20 Nm |
Cable lug connection according to standard | DIN 46235 |
Min. cross section for cable lug connection | 10 mm² |
Max. cross section for cable lug connection | 95 mm² |
Bolt length | 26 mm |
Bolt diameter | 10 mm |
Tightening torque, min | 10 Nm |
Tightening torque max | 20 Nm |
Cable lug connection according to standard | DIN 46237 |
Max. cross section for cable lug connection | 6 mm² |
Bolt length | 26 mm |
Bolt diameter | 10 mm |
Tightening torque, min | 10 Nm |
Tightening torque max | 20 Nm |
Screw thread | M10 |
Tightening torque, min | 10 Nm |
Tightening torque max | 20 Nm |
Standards and Regulations
Connection in acc. with standard | CSA |
---|---|
IEC 60947-7-1 | |
Flammability rating according to UL 94 | V0 |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 – HL 3 |
Environmental Product Compliance
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |