Key Commercial Data
Orderkey | 2905051 |
---|---|
Packing unit | 10 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 90 (IF-2005) |
GTIN | 4017918079192 |
Weight per Piece (excluding packing) | 25.210 g |
Custom tariff number | 85364900 |
Country of origin | DE (Germany) |
Ambient conditions
Ambient temperature (operation) | -20 °C … 60 °C |
---|---|
Ambient temperature (storage/transport) | -20 °C … 70 °C |
Input data
Nominal input voltage UN | 110 V DC |
---|---|
Input voltage range in reference to UN | 0.8 … 1.2 |
Input voltage range | 88 V DC … 132 V DC |
Switching threshold “0” signal in reference to UN | ≤ 0.4 |
Switching threshold “1” signal in reference to UN | ≥ 0.8 |
Typical input current at UN | 6 mA |
Typical response time | 20 µs |
Typical turn-off time | 200 µs |
Status display | Yellow LED |
Type of protection | Reverse polarity protection |
Surge protection | |
Protective circuit/component | Polarity protection diode |
Transmission frequency | 500 Hz |
Output data
Output voltage range | 12 V DC … 60 V DC |
---|---|
Limiting continuous current | 1 A (see derating curve) |
Surge current | 5 A (t = 1 s) |
Peak offstate voltage | 60 V DC (Collector-emitter reverse voltage) |
Voltage drop at max. limiting continuous current | 1.2 V |
Output circuit | 2-wire, floating |
Type of protection | Reverse polarity protection |
Surge protection | |
Protective circuit/component | Polarity protection diode |
General
Test voltage input/output | 2.5 kV AC |
---|---|
Mounting position | any |
Standards/regulations | DIN VDE 0110b, Gr. C for 250 V DC |
DIN VDE 0160 (in relevant parts) |