Key Commercial Data
Orderkey | 2961192 |
---|---|
Packing unit | 10 pc |
Minimum order quantity | 10 pc |
Catalog page | Page 304 (C-5-2017) |
GTIN | 4017918158019 |
Weight per Piece (excluding packing) | 15.940 g |
Custom tariff number | 85364190 |
Country of origin | AT (Austria) |
Ambient conditions
Ambient temperature (operation) | -40 °C … 85 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Coil side
Nominal input voltage UN | 24 V DC |
---|---|
Typical input current at UN | 17 mA |
Typical response time | 7 ms |
Typical release time | 3 ms |
Coil resistance | 1440 Ω ±10 % (at 20 °C) |
Power dissipation for nominal condition | 0.41 W |
Contact side
Contact type | 2 PDT |
---|---|
Type of switch contact | Single contact |
Contact material | AgNi |
Maximum switching voltage | 250 V AC/DC |
Minimum switching voltage | 5 V (at 10 mA) |
Min. switching current | 10 mA (At 5 V) |
Maximum inrush current | 25 A (20 ms) |
Limiting continuous current | 8 A |
Interrupting rating (ohmic load) max. | 190 W (at 24 V DC) |
85 W (at 48 V DC) | |
60 W (at 60 V DC) | |
44 W (at 110 V DC) | |
60 W (at 220 V DC) | |
2000 VA (for 250 V AC) | |
Switching capacity | 2 A (at 24 V, DC13) |
0.2 A (at 250 V, DC13) | |
3 A (at 24 V, AC15) | |
3 A (at 120 V, AC15) | |
3 A (at 250 V, AC15) | |
Motor load according to UL 508 | 1/4 HP, 120 V AC |
1/2 HP, 240 V AC |
General
Test voltage relay winding/relay contact | 5 kV AC (50 Hz, 1 min.) |
---|---|
Test voltage relay contact/relay contact | 2.5 kV AC (50 Hz, 1 min.) |
Operating mode | 100% operating factor |
Degree of protection | RT III (wash-proof) |
Mechanical service life | 3x 107cycles |
Service life, electrical | see diagram |
Mounting position | any |
Assembly instructions | Can be aligned without spacing (> 70 °C ≥ 2.5 mm) |
Net weight (SAP) | 15.94 g |